Baby oxygen mix-up: Bankstown-Lidcombe Hospital engineer stood down over fatal error.

By state political reporter Sarah Gerathy

An engineer at a Sydney hospital has been stood down over a fatal oxygen mix-up in the birthing unit and NSW Health has ceased using the company that installed the gas lines involved.

Last month, NSW Health confirmed three newborn babies were affected during incidents with the oxygen supply outlets at Bankstown-Lidcombe Hospital in Sydney’s south-west.

One infant died and another suffered suspected brain damaged when they were accidentally given nitrous oxide — also known as laughing gas — instead of oxygen from gas lines installed in the birthing suite.

The State Government has released an interim report into the mix-up, stating the engineer involved in commissioning the gas line had been stood down, pending the outcome of the investigation.

The interim report also confirmed NSW Health had stopped using the company BOC Ltd for installation, commissioning and testing works at all hospitals across the state until the investigation was completed.

Health Minister Jillian Skinner said it appeared both the hospital and the company that installed the gas were to blame.

NSW Opposition Leader Luke Foley has called on Ms Skinner to resign over the mix-up and the revelations of more than 100 cases of chemotherapy under-dosing in the state’s hospitals.

Coronial inquest to examine if other staff to blame

Ms Skinner said the full investigation and a coronial inquest into the baby boy’s death would help identify whether other hospital managers or staff contributed to the tragedy.

“If so, they’ll be held to account,” she said.

The gas lines had been installed after an oxygen bottle ran out in a birthing suite while a baby was being resuscitated in January 2014.

ADVERTISEMENT

That baby survived the incident.

Ms Skinner said every medical gas outlet installed in NSW Health facilities over the past five years was now being checked to ensure the correct gas was being emitted.

She said a state-wide audit had also been extended to every medical gas outlet in NSW, irrespective of when it was installed.

The Minister said any future upgrade to medical gas outlets in NSW public hospitals would be required to undergo independent verification.

The State Opposition has declared it will move immediately for an Upper House inquiry into the incidents, saying the internal investigation the Minister ordered is inadequate.

Labels wrong before installation: BOC Ltd

In a statement, BOC said it was “extremely saddened by the tragic death” of the newborn and by the injury of another at the hospital.

The company said the incorrect labels on the gas pipelines were attached before their installation at the hospital.

“The original installation of pipes was not conducted by BOC.

“The July 2015 project documentation indicates that both a hospital representative and a BOC contractor were involved in the commissioning of the single oxygen outlet where the fault was found.”

The company said it would increase the level of testing in every new gas pipeline installation.

The full report is due to be completed by August 25.